3.2 Commands Details
3-33
3
Commands for Preparation Process
(3) How to Send an ADJ Command for Monitoring Data
The table below lists the data that can be monitored.
ADJ Command Execution Procedure for Monitoring Data:
1. Set the reference address to be monitored, and send the ADJ command.
CCMD = 0003H
CADDRESS = Reference address
When the slave station receives the command normally
,
CMDRDY of status field will be see to 1. Also
check ERRCODE.
2. When the command transmissi
on
is completed normally, CDATA of RSP will be read out for CSIZE to
obtain the data.
List of Data that Can be Monitored
Name
Reference
Address
Data
Size
Unit Remarks
Motor capacity
C00FH (Lower-
most)
C010H (Upper-
most)
2 bytes [W]
Motor voltage C011H 2 bytes [V]
Motor rated speed C01CH 2 bytes
Rotary motor: [×10
C01EH reference value
min
-1
]
Linear motor: [×10
C01EH reference value
mm / s]
Motor max. speed C01DH 2 bytes
Rotary motor: [×10
C01EH reference value
min
-1
]
Linear motor: [×10
C01EH reference value
mm / s]
Motor speed exponent C01EH 2 bytes −
Motor rated torque
(force)
C01FH 2 bytes
Rotary servomotor: [×10
C021H reference value
N.m]
Linear servomotor: [×10
C021H reference value
N]
Motor torque (force)
exponent
C021H 2 bytes −
Encoder resolution
C022H (Lower-
most)
C023H (Upper-
most)
2 bytes
Rotary servomotor: [pulse / rev]
Linear servomotor: [pulse / pitch]
Note:
When fully-
closed setting is
enabled
(Pn002.3≠0), the
unit is [pulse /
pitch]
Maximum motor
torque (force) that can
be output
E701H 2 bytes [%]
Motor max. output
speed
C027H 2 bytes
Rotary servomotor: [×10
C01EH reference value
min
-1
]
Linear servomotor: [×10
C01EH reference value
mm / s]
Linear scale pitch E084H 4 bytes
[×10
E 086H reference value
pm / pitch]
For linear servo-
motors only
Linear scale pitch
exponent
E086H 2 bytes −
For linear servo-
motors only
Details of Command to Monitor Data
Command Response
CCMD/CANS CCMD = 03H CANS = 03H (copy of the command)
CADDRESS Reference address Reference address (copy of the command)
CSIZE/
ERRCODE
– (Not required)
At normal reception: SIZE (2 or 4)
At error occurrent: A value other than 2 and 4
CDATA/RDATA – (Not required) Reference data