Object ID Object Name
Modbus
Address
Active Text Inactive Text PV Access
BV66 BYP Drive Select CMD 8400H: bit 9 ON OFF C
BV67 BYP Auto Select CMD 8400H: bit 10 ON OFF C
BV68 Not Used BV68 8400H: bit 11 ON OFF C
BV69 BYP BYPASS Sel CMD 8400H: bit 12 BYP DRV C
BV70 BYP Fault Reset CMD 8400H: bit 13 ON OFF C
BV71 BYP Ext Fault CMD 8400H: bit 14 ON OFF C
BV72
<2>
BYP DI-01 Command 8402H: bit 0 ON OFF W
BV73
<2>
BYP DI-02 Command 8402H: bit 1 ON OFF W
BV74
<2>
BYP DI-03 Command 8402H: bit 2 ON OFF W
BV75
<2>
BYP DI-04 Command 8402H: bit 3 ON OFF W
BV76
<2>
BYP DI-05 Command 8402H: bit 4 ON OFF W
BV77
<2>
BYP DI-06 Command 8402H: bit 5 ON OFF W
BV78
<2>
BYP DI-07 Command 8402H: bit 6 ON OFF W
BV79
<2>
BYP DI-08 Command 8402H: bit 7 ON OFF W
BV80 BYP HAND Mode Status 8784H: bit 0 ON OFF R
BV81 BYP OFF Mode Status 8784H: bit 1 ON OFF R
BV82 BYP AUTO Mode Status 8784H: bit 2 ON OFF R
BV83 BYP DRV Mode Status 8784H: bit 3 ON OFF R
BV84 BYP BYPASS Mode Stat 8784H: bit 4 ON OFF R
BV85 BYP Smk Prg BYP Stat 8784H: bit 5 ACTIVE OFF R
BV86 BYP Smk Prg DRV Stat 8784H: bit 6 ACTIVE OFF R
BV87 BYP Safety Status 8784H: bit 7 OPEN CLOSED R
BV88 BYP BAS Interlk Stat 8785H: bit 0 OPEN CLOSED R
BV89 BYP RUN Status 8785H: bit 1 RUN OFF R
BV90 BYP Fault Status 8785H: bit 2 FAULT OFF R
BV91 BYP Auto Xfer Status 8785H: bit 3 ACTIVE OFF R
BV92 BYP Remote Xfer Stat 8785H: bit 4 ACTIVE OFF R
BV93 BYP Energy Save Stat 8785H: bit 5 ACTIVE OFF R
BV94 BYP Motor 1 Sel Stat 8785H: bit 6 SELECT OFF R
BV95 BYP Motor 2 Sel Stat 8785H: bit 7 SELECT OFF R
BV96 BYP Drive Flt Status 8786H: bit 0 FAULT OFF R
BV97 BYP Safety Flt Stat 8786H: bit 1 FAULT OFF R
BV98 BYP BAS ILock Status 8786H: bit 2 FAULT OFF R
BV99 BYP Ext Fault Stat 8786H: bit 3 FAULT OFF R
BV100 Not Used BV100 8786H: bit 4 FAULT OFF R
BV101 BYP Motor OL Stat 8786H: bit 5 FAULT OFF R
BV102 BYP Motor 1 OL Stat 8786H: bit 6 FAULT OFF R
BV103 BYP Mtr 2 OL Stat 8786H: bit 7 FAULT OFF R
BV104 BYP Input Phase Loss 8787H: bit 0 FAULT OFF R
BV105 BYP Drive Comms 8787H: bit 2 FAULT OFF R
BV106 BYP Loss Of Load 8787H: bit 5 FAULT OFF R
BV107 BYP Option Brd Comms 8787H: bit 3 FAULT OFF R
<1> Refer to Accessing Bypass Parameters and the Enter Command on page 370 for an explanation of how to read and write drive parameters not
listed in the analog or binary objects.
<2> Object is disabled when Z3-12 is set to 0 in bypass controller software versions VST800298 and later.
u
Device Object
The Device Object fully describes the BACnet device to the network. Notable is that the Device Object Instance ID and the
Device Object Name are configurable.
C.6 BACnet Objects Supported
368
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual
Zobrazit stránku 367
1 2 ... 363 364 365 366 367 368 369 370 371 372 373 ... 461 462

Komentáře k této Příručce

Žádné komentáře