A.4 Drive Derating Data
The drive can be operated at above the rated temperature, altitude, and default carrier frequency by derating the drive capacity.
u
Carrier Frequency Derating
Derate the drive according to Figure A.1 to Figure A.3 as the carrier frequency increases above the factory default setting.
12.5 kHz5 kHz
100%
60%
0
Figure A.1 Carrier Frequency Derating (Z1B1D002 to D114 and B001 to B096)
8 kHz5 kHz
100%
80%
10 kHz0
Figure A.2 Carrier Frequency Derating (Z1B1D143 to D173 and B124 to B180)
4kHz
100%
60%
10kHz0
Figure A.3 Carrier Frequency Derating (Z1B1B240 and B302)
u
Altitude Derating
The drive standard ratings are valid for installation altitudes up to 1000 m. For installations from 1000 m to 3000 m, the drive
rated output current must be derated for 0.2% per 100 m.
A.4 Drive Derating Data
304