9.8 Receive Message Function (MSG-RCV)
9-26
Status (PARAM01)
Output the status of the transmission unit. See 5.5.1."Parameters" of "Status (PARAM01)" for
details.
Called Station # (PARAM02)
The station number of sending side is output.
Function Code (PARAM04)
Output the MEMOBUS function code received. Refer to Table 9.13.
Table 9.13 Function Codes
Function Code Setting
00H Unused ×
01H Read coil status
02H Read input relay status
03H Read contents of holding register
04H Read contents of input register
05H Change status of single coil
06H Write into a single holding register
07H Unused
×
08H Loop-back test
09H Read contents of holding register (expanded)
0AH Read contents of input register (expanded)
0BH Write into holding register (expanded)
0CH Unused ×
0DH Discontinuous readout of holding register (expanded)
0EH Discontinuous write into holding register (expanded)
0FH Change status of a multiple coil
10H Write into a plurality of holding register
11H to 20H Unused
×
21H to 3FH System reserved
×
40H to 4FH System reserved
×
50H to Unused ×
Note :
The MB, MW, IB, and IW registers can be used respectively as the coil, holding register,
input relay, and input registers during slave operation.
Data Address (PARAM05)
The data address requested by the sending side is output.
Data Size (PARAM06)
The data size (number of bits or number of words) of the requested read or write is output.
Called CPU # (PARAM07)
The called CPU NO. is output.
Coil Offset (PARAM08)
Set the offset word address of the coil. This is valid in the case of function codes 01H, 05H, and
0FH.