9.6 Inverter Trace Read Function (ITRC-RD)
9-13
9.6 Inverter Trace Read Function (ITRC-RD)
[Outline]
Reads out the trace data of the inverter and stores this data in the user registers. The data in the trace
buffer can be read out upon designating the number of records needed. The readout can be performed
upon designating just the necessary items in the record.
[Applicable inverters] : MP930, SVB-01, connected via 215IF
[Format]
Symbol : ITRC-RD
Full Name : Inverter-Trace Read
Category : SYSTEM
Icon :
[Parameter]
I/O
Definition
Parameter Name
I/O
Designation
Setting
Execute B-VAL Inverter trace read command
Abort B-VAL Inverter trace read forced interruption command
Type of transmission device
Dev-Typ I-REG
215IF = 1 MP930 = 4 SVB-01 = 11
Line No.
Cir-No I-REG
215IF = 1 MP930 = 1 SVB-01 = 1 to 16
Slave station No.
St-No I-REG
215IF = 1 to 64 MP930 = 1 to 14 SVB-01 = 1 to 14
Transmission buffer channel No. (No designation)
Ch-No I-REG
215IF = 1 to 3 MP930 = 1 SVB-01 = 1 to 8
Rec-Size I-REG Number of records to be read (1 to 64)
Select I-REG Items to be read (0001H to FFFFH)
Bits 0 to F correspond to trace data items 1 to 26
Input
Dat-Adr Address input Head address of data buffer register (address of MW or DW)
Busy B-VAL The reading of inverter trace data is in progress.
Complete B-VAL Completion of inverter trace read
Error B-VAL Occurrence of error
Status I-REG Inverter trace read execution status
Rec-Size I-REG Number of read records
Output
Rec-Len I-REG Length of read record (for 1 record)
Komentáře k této Příručce