9.7 Send Message Function (MSG-SND)
9-18
REQUEST
1 = Request
0 = Completion of receipt report
Called Station # (PARAM02)
Serial
1254 : Message is sent to the station of designated device address.
Function Code (PARAM04)
The MEMOBUS function code to be sent is set. Refer to Table 9.9.
Table 9.9 Function Codes
Function Code Setting
00H Unused
×
01H Read coil status
02H Read input relay status
03H Read contents of holding register
04H Read contents of input register
05H Change status of single coil
06H Write into a single holding register
07H Unused ×
08H Loop-back test
09H Read contents of holding register (expanded)
0AH Read contents of input register (expanded)
0BH Write into holding register (expanded)
0CH Unused
×
0DH Discontinuous readout of holding register (expanded)
0EH Discontinuous write into holding register (expanded)
0FH Change status of a multiple coil
10H Write into a plurality of holding register
11H to 20H Unused
×
21H to 3FH System reserved
×
40H to 4FH System reserved ×
50H to Unused
×
(× : cannot be set, :can be set)
Note : Only MW (MB) can be used as the sending/receiving register during master operation. The
MB, MW, IB, and IW registers can be used respectively as the coil, holding register, input