72 VS-616G5 Programming Manual
Section F: Option Parameters
F6 DO-08 Option Set-up
F6 DO-08 Set-up
Selects the multi-function output selections for the DO-08 option.
* When F6-01 is set to binary output (setting = “1”), use the table below to read the DO-08 output.
Note: When the terminal is open, the bit setting is “0”; when the terminal is closed, the bit setting is “1”.
F6-01 DO-08 Digital Output Selection DO-08 Selection
A A A A
Setting Terminal No. Description
0
8-channel
individual
(factory default)
TD5/TD11 Overcurrent (SC, OC, GF)
TD6/TD11 Overvoltage (OV)
TD7/TD11 Inverter overload (OL2)
TD8/TD11 Fuse blown (FU)
TD9/TD11 Not used
TD10/TD11 Inverter overheat (OH)
TD1/TD2 During zero-speed detection
TD3/TD4 During speed agree
1
binary output
TD5/TD11
Binary output *
TD6/TD11
TD7/TD11
TD8/TD11
TD9/TD11 During zero-speed detection
TD10/TD11 During speed agree
TD1/TD2 During run
TD3/TD4 Minor fault
TD8/TD11
(bit 3)
TD7/TD11
(bit 2)
TD6/TD11
(bit 1)
TD5/TD11
(bit 0)
Description
0 0 0 0 No fault
0 0 0 1 Overcurrent (SC, OC, GF)
0 0 1 0 Overvoltage (OV)
0 0 1 1 Inverter overload (OL2)
0 1 0 0 Inverter overheat (OH)
0 1 0 1 Overspeed (OS)
0 1 1 0 Fuse blown (FU)
0 1 1 1 Not used
1 0 0 0 External fault (EF3 ~ EF8)
1 0 0 1 Controller fault
1 0 1 0 Motor overload (OL1)
1 0 1 1 Not used
1 1 0 0 Power loss (UV1, UV2, UV3)
1 1 0 1 Excessive speed deviation (DEV)
1 1 1 0 PG disconnection (PGO)
1 1 1 1 Not used