VS-616G5 Programming Manual 35
V/f V/f w/PG
Open Loop
Vector
Flux
Vector
Parameter C3-05 determines if the motor torque characteristic is based on output frequency or motor
speed.
When running the motor only in the constant torque region, leave parameter C3-05 set to 0 for the
best performance.
When running the motor in the constant horsepower region, set parameter C3-05 to 1 because the
larger flux will result in better motor stability.
C3-04 Slip Compensation During Regeneration Slip Comp Regen
A - A -
Setting Description
0 Slip compensation disabled during regeneration (factory default)
1 Slip compensation enabled during regeneration
C3-05 Flux Calculation Method Flux Select
- - A -
Setting Description
0 Slip Included
Motor torque characteristic is based on frequency. (factory default)
1 Slip Excluded
Motor torque characteristic is based on motor speed.
60Hz 1800 rpm 120Hz 3600 rpm
=1=0
=0
=1
Torque
100%
0%
Section C: Tuning Parameters
C3 Motor Slip Compensation