5 Parameter Setting and Functions
5.4.6 Fully-closed Loop Control
5-20
5.4.6 Fully-closed Loop Control
For more information on the settings for fully-closed loop control, refer to
Σ
-V Series Users Manual Design
and Maintenance Rotational Motor/Command Option Attachable Type (SIEP S800000 60).
When using the fully-closed loop control with an INDEXER Module, some restrictions apply to the setting
for parameter Pn20A (External Encoder Pitches.)
Set parameter Pn20A (External Encoder Pitches) to a value within the recommended
range. If a value outside of this range is set, the speed reference may be limited to a
value lower than the maximum speed of the motor.
Scale Type PGTYPE Response
Pn20A Setting
Range
8-bit serial converter unit
8-bit scale
PGTYPE = 0000xx08 Pn20A 65103
9-bit scale PGTYPE = 0000xx09 Pn20A 32551
10-bit scale PGTYPE = 0000xx0A Pn20A 16275
13-bit scale PGTYPE = 0000xx0D Pn20A 2034