Yaskawa MP2000 Series I/O Module User Manual Uživatelský manuál Strana 88

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 139
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 87
4.1 Outline of LIO-06 Module
4.1.4 LED Indicators
88
( 2 ) Environmental Conditions
4.1.4 LED Indicators
The following table shows the LIO-06 Module status when each indicator lamp is lit or unlit.
Item Specifications
Environmental
Conditions
Ambient Operating
Temperature
0 to 50°C
Ambient Storage
Temperature
-25 to 85°C
Ambient Operating
Humidity
30% to 95% (with no condensation)
Ambient Storage
Humidity
5% to 95% (with no condensation)
Pollution Level Pollution level 1 (conforming to JIS B 3501)
Corrosive Gas There must be no combustible or corrosive gas.
Operating Altitude 2,000 m above sea level or lower
Mechanical Operating
Conditions
Vibration Resistance
Conforming to JIS B 3502:
10 to 57 Hz with single-amplitude of 0.075 mm
57 to 150 Hz with fixed acceleration of 9.8 m/s
2
10 sweeps each in X, Y, and Z directions
(sweep time: 1 octave/min)
Shock Resistance
Conforming to JIS B 3502:
Peak acceleration of 147 m/s
2
twice for 11 ms each in the X, Y, and Z direc-
tions
Electrical Operating
Conditions
Noise Resistance
Conforming to EN 61000-6-2, EN 55011 (Group 1, Class A)
Power supply noise (FT noise): 2 kVmin., for one minute
Radiation noise (FT noise): 1 kVmin., for one minute
Ground noise (impulse noise): 1 kVmin, for 10 minutes
Electrostatic noise (contact discharge): 4 kVmin, for 10 times
Installation
Requirements
Ground Ground to 100 Ω max.
Cooling Method Natural cooling
Indicator Color When Lit When Unlit
RUN Green
Normal operation Operation stopped
ALM Red
Error occurrence (Lights when one of
the following errors occurs)
•Blown fuse
ASIC error for counter/AO
Oscillator error
Phases A and B disconnection
Normal operation
ALMRUN
Zobrazit stránku 87
1 2 ... 83 84 85 86 87 88 89 90 91 92 93 ... 138 139

Komentáře k této Příručce