YASKAWA TM.iQp.07 iQpump Controller Programming Manual 33
b5-01 PI Mode
The iQpump drive can be used as a stand-alone PI controller. If PI functionality is selected by parameter b5-01, the iQpump drive will
adjust its output to cause the feedback from a transmitter to match the PI Setpoint (b5-19). The setting of b5-01 will determine whether PI
functionality is disabled (b5-01 = “0: Disabled”), enabled (b5-01 = “1: Enabled”), enabled - 2 zone (dual zone PI enabled) (b5-01 = 2).
b5-01 = 0, Disabled
PI functionality is disabled.
b5-01 = 1, Enabled (factory default)
PI functionality is enabled.
b5-01 = 2, Enabled - 2 Zone (dual zone PI enabled)
<0034>
Enabled - 2 zone.
Provides automatic setpoint and feedback switching for dual zone pumping applications (geothermal).
Terminal A1 is used as a feedback signal for “Zone 1”.
Standard PI Feedback (H3-09 = B) as feedback for “Zone 2”.
Based upon the two feedback levels, the drive determines which setpoint and feedback signal to use.
Figure 1.27
Figure 27. Dual Zone PI
Changes from standard product:
When the Dual Zone PI is enabled (b5-01 = 2) Terminal A1 becomes the feedback signal for Zone 1.
Multi-Step Frequency Reference Select digital inputs are ignored (H1-0x = 3 or 4) when the Dual Zone PI is enabled (b5-01 = 2).
Transducer Loss Detection is enabled on Terminal A1 when b5-01 = 2.
Setting Description
0Disabled
1 Enabled (factory default)
2 Enabled - 2 Zone (dual zone PI enabled)
<0034>
To:
Zone 1
To:
Zone 2
Zone 1
Valve
Zone 2
Valve
Yaskawa
iQpump Drive
A1
A2
T1 T2 T3
Motor Leads
Motor
Pump